Most sealed NiMH packs used around radar and radio sites are not designed — they are copied. A previous product's 4 Ah pack becomes the next product's 4 Ah pack, the cell count is whatever the old charger expects, and the capacity is whatever fits the enclosure. The pack then works in the lab, degrades in a hot shelter, and fails in the third winter. This paper sets out a sizing method that starts from the duty the pack actually has to perform, applies the derating stack in the right order, and ends with a charging and protection design that matches the chemistry rather than fighting it.
Field returns from this segment cluster around five causes, and only one of them is a cell-quality problem.
| Failure mode | What actually happened | Design fix |
|---|---|---|
| Capacity shortfall in winter | Pack sized at 25 °C; site ambient −10 °C; NiMH delivers materially less usable capacity when cold | Cold derating in the calculation; insulation or heater where justified |
| Early death in a hot shelter | Continuous trickle at elevated temperature; electrolyte dry-out and separator degradation | Lower trickle or intermittent top-up; thermal placement away from heat sources |
| One cell fails, whole string dies | No cell matching, no per-cell monitoring; a weak cell reverses on deep discharge | Matched cells from one lot; pack-level LVD; periodic capacity test |
| Charger never terminates | Charger designed for NiCd (−ΔV too small to detect on NiMH); pack overheats | Temperature-rise or timer termination; charger marked for NiMH |
| Connector or wiring loss | Voltage drop at high pulse current; connector heating | Size on peak current, not average; crimp and test |
None of these are solved by buying a more expensive cell. They are solved by writing the duty down before the pack is specified.
Every station support pack does one of three jobs. Decide which, because the sizing maths and the chemistry trade-offs are different for each.
| Duty class | Typical station example | Energy needed | Dominant constraint |
|---|---|---|---|
| Hold-up | Keep a handheld terminal alive across a mains transfer; bridge a reboot | Watt-hours, small | Power delivery and voltage sag, not capacity |
| Portable shift power | Test instrument or handheld radio for one shift | Tens of watt-hours | Energy density and swap logistics |
| Autonomy | Remote auxiliary node running for a day or more between charges | Hundreds of watt-hours | Self-discharge, cold, and enclosure volume |
A hold-up pack is sized by current and internal resistance. A shift pack is sized by energy. An autonomy pack is sized by energy plus self-discharge plus the solar or mains recharge window. Mixing the three is how a 4 Ah pack ends up proposed for a 24-hour node.
A load audit for a station pack should capture four categories: continuous, intermittent, pulse, and parasitic. The last one is the one that ruins autonomy calculations — a monitoring board, a status LED and a leaking input capacitor can easily add 10 to 30 percent to a small load.
| Load category | Example | How to measure | How to use it |
|---|---|---|---|
| Continuous | Receiver, sensor, monitoring board | DMM or logging power meter over 10 min | Average current × hours |
| Intermittent | Transmit bursts, display backlight, motor | Duty-cycle the measurement | Energy per event × events per shift |
| Pulse | Radio transmit, camera flash, solenoid | Current probe with capture | Peak current for connector and protection; energy for capacity |
| Parasitic / standby | Sleep current, LED, leakage | µA meter in sleep mode | Multiply by the full standby period — often the largest term |
Two practical rules. First, measure at the pack terminals, not at the device input, so that converter losses are included. Second, measure at the temperature the pack will actually see; a load that draws 200 mA at 25 °C may draw more at −20 °C if it contains a switching converter with a fixed output power.
Sealed NiMH is one option among several, and the honest comparison table looks like this.
| Attribute | Sealed NiMH | VRLA lead-acid | LiFePO4 | Li-ion (NMC/LCO) | Primary lithium |
|---|---|---|---|---|---|
| Nominal cell voltage | 1.2 V | 2.0 V | 3.2 V | 3.6/3.7 V | 3.0–3.6 V |
| Energy density (order) | Moderate | Low | High | High | Very high |
| Pulse capability | Good | Moderate | Good | Good | Limited |
| Cold performance | Reduced below 0 °C | Reduced | Reduced but better | Reduced | Reduced |
| Float / trickle tolerance | Poor to moderate | Good | Moderate (needs BMS) | Poor (needs BMS) | Not applicable |
| Transport | UN 3496, not restricted by air in many cases | UN 2794, class 8 | UN 3480/3481, class 9 | UN 3480/3481, class 9 | Class 9 in many formats |
| End-of-life | Nickel recycling; no cadmium, no lead | Lead recycling, regulated | Lithium recycling, evolving | Lithium recycling, evolving | Mixed |
| Best station role | Instruments, handhelds, small nodes, training | Main DC plant, UPS | Main DC plant, high-cycle | Compact high-energy devices | Long-standby, single-use |
The table explains why NiMH keeps a role even where lithium is cheaper per watt-hour: it is a mature, abuse-tolerant, low-voltage chemistry with no mandatory battery management electronics, no pressurised cell, and a transport classification that does not require a UN 38.3 test summary for every shipment. For a maintenance instrument that is charged nightly and dropped occasionally, those properties are worth more than the last 20 percent of energy density.
NiMH strings are built from 1.2 V cells, and the voltage that matters is the end-of-discharge voltage, not the nominal. A cell that is nominally 1.2 V is around 1.0 V at the end of a practical discharge under load, and can be lower at high rate or low temperature. Equipment that needs a minimum 10.8 V, for example, cannot be fed from a 9-cell string that ends at 9.0 V.
| String | Nominal | Approx. end-of-discharge (1.0 V/cell) | Typical station use |
|---|---|---|---|
| 3S | 3.6 V | 3.0 V | Small sensor, LED task light |
| 6S | 7.2 V | 6.0 V | Handheld radio, legacy instrument |
| 10S | 12.0 V | 10.0 V | 12 V test equipment |
| 12S | 14.4 V | 12.0 V | 14.4 V instrument pack |
| 20S | 24 V | 20 V | 24 V auxiliary node |
| 40S | 48 V | 40 V | 48 V buffer, DC-DC-fed node |
Two configuration rules that are routinely broken:
The 40S case deserves a note because it looks like a telecom drop-in. Forty NiMH cells at the -48 V plant's -53.5 V float works out to about 1.34 V per cell, which is inside the range some NiMH designs will tolerate continuously. But tolerance is not the same as suitability: NiMH does not like sustained overcharge at elevated temperature, and a pack sitting on a live bus for years will lose electrolyte and capacity. If a NiMH pack must coexist with a -48 V bus, feed it through a dedicated charger or a DC-DC stage with its own charge control; do not hang it directly on the plant and call it a battery.
The calculation is a chain, and the order matters:
Crequired (Ah) = Eload (Wh) ÷ Vaverage ÷ (ηtemp × ηrate × ηEOL × ηwiring)
where Vaverage is the average discharge voltage (roughly 1.15–1.2 V per cell for a slow discharge, lower at high rate), and the efficiency factors are all less than one.
| Factor | Typical value | When to use it |
|---|---|---|
| Temperature, ηtemp | 0.85 at 0 °C; 0.70–0.75 at −20 °C; 1.0 at 20–25 °C | Always if the site goes below 10 °C |
| Rate, ηrate | 0.85–0.95 | Discharge faster than about C/2 |
| End of life, ηEOL | 0.80–0.85 | Always — a pack is replaced at 80 % capacity, not at 0 % |
| Wiring and connector, ηwiring | 0.95–0.98 | Always; lower for long leads or high pulse current |
| Self-discharge over standby | 1–3 %/month (LSD); 20–30 %/month (standard) | Autonomy packs that sit for weeks |
Worked example 1 — portable test terminal, illustrative. A 14.4 V (12S) instrument draws 8 W average over a 6-hour shift, so 48 Wh. With ηtemp 0.85 at a cold site, ηrate 0.95, ηEOL 0.85 and ηwiring 0.97, the denominator is about 0.665, so the pack must store about 72 Wh. At an average discharge voltage of 13.8 V that is 5.2 Ah, so the nearest standard size is 5.5 or 6 Ah rather than the 4 Ah the previous product used.
Worked example 2 — auxiliary sensor node, illustrative. A 24 V (20S) node draws 3 W continuously and must run 24 hours between visits: 72 Wh. With the same stack the requirement is about 108 Wh, or 4.5 Ah at 24 V. Adding a 2 W heater for winter would double it; adding a parasitic 20 mA standby load at 24 V adds 11.5 Wh per day, which is 16 percent — enough to erase the margin if it is left out.
Worked example 3 — hold-up, illustrative. A 12 V terminal drawing 20 W must ride through a 10-minute transfer: 3.3 Wh. After derating, about 5 Wh, or 0.4 Ah at 12 V. The pack is tiny; the real design question is whether its internal resistance can deliver the 20 W without dropping below the terminal's brown-out threshold. That is a current question, not a capacity question.
| Example | Load | Raw energy | Derated energy | Resulting capacity |
|---|---|---|---|---|
| Test terminal, 6 h shift | 8 W average | 48 Wh | ≈72 Wh | ≈5.2 Ah at 13.8 V (choose 5.5–6 Ah) |
| Sensor node, 24 h autonomy | 3 W continuous | 72 Wh | ≈108 Wh | ≈4.5 Ah at 24 V |
| Terminal hold-up, 10 min | 20 W | 3.3 Wh | ≈5 Wh | ≈0.4 Ah at 12 V; check IR |

Illustrative animation — how temperature, rate, end-of-life and wiring factors reduce usable capacity. Not measured data.
NiMH charging is a current-limited process with a termination event. The three accepted termination methods are voltage drop (−ΔV), temperature rise (dT/dt), and a timeout; a good charger uses at least two of them.
| Parameter | Typical value | Notes |
|---|---|---|
| Fast charge rate | 0.5–1 C | Only with temperature sensing and −ΔV detection |
| −ΔV termination | 5–10 mV per cell | Small on NiMH; easy to miss at low charge rates |
| dT/dt termination | ≈1 °C per minute | The most reliable signal in a hot enclosure |
| Timer backup | ≈1.2 × expected charge time | Prevents indefinite overcharge if detection fails |
| Trickle after full charge | 0.03–0.05 C, or intermittent top-up | Lower is better in a hot shelter |
| Charge temperature window | 0–40 °C, with reduced rate at the ends | Do not fast-charge a frozen pack |
| Cell end voltage | ≈1.4–1.45 V per cell at full charge | Open-circuit, after rest |
A charger designed for NiCd will usually fail on NiMH: the voltage drop at full charge is smaller, and a NiCd charger's fixed timer will overcharge a NiMH pack that self-heats. If a station's existing charger cannot be reconfigured, the pack should be built to the charger's profile rather than the other way round.
The minimum protection set for a station support pack is:
Pack-level protection is not a substitute for a correctly designed charger, and a charger is not a substitute for pack-level protection. They cover different faults: the charger covers overcharge, the pack covers over-discharge, short circuit and external abuse.
| Detail | Recommendation | Why |
|---|---|---|
| Cell spacing | Leave a gap between cells; avoid a solid potted block | NiMH generates heat at the end of charge; a potted block traps it |
| Thermal sensor placement | Centre of the pack, bonded to a cell can | Edge placement reads the enclosure, not the cells |
| Enclosure | IP54 minimum for shelter use; IP65+ for outdoor nodes | Dust and humidity dominate field failures |
| Vibration | Spot-welded tabs, no free wire, conformal coat the board | Vehicle-mounted and antenna-adjacent packs see continuous vibration |
| Serviceability | Replaceable pack, labelled with chemistry, voltage and date code | Prevents a lithium charger being used on a NiMH pack |

Illustrative animation — NiMH charge termination by voltage drop and temperature rise. Not a measured curve.
Mechanically it fits the voltage window, but it is not a plant battery. NiMH tolerates continuous float less well than VRLA, has different charge termination needs, and is not available in the ampere-hour sizes a plant is designed around. Use it behind a dedicated charger or DC-DC stage, not directly on the bus.
Plan on roughly 85 percent at 0 °C and 70 to 75 percent at −20 °C for a moderate discharge rate. High-rate discharges lose more. The exact figure depends on the cell, so ask for the discharge curve at the target temperature rather than a single number.
For autonomy packs that sit for weeks between charges, yes — the difference between 1–3 percent per month and 20–30 percent per month is the difference between a 24-hour node and a 3-day node. For a pack charged every night, standard cells are usually fine.
As few as possible. Parallel strings hide a weak cell and complicate protection. If capacity demands it, use parallel cells within a group with individual fusing, and keep the group small.
Not in the lithium sense — there is no cell-level semiconductor switching in a typical NiMH pack. It does need a charger with the right termination, a pack-level LVD, a fuse and a temperature sensor. That set is simpler and cheaper than a lithium BMS, which is part of NiMH's appeal for low-cost station devices.
Several hundred to about a thousand cycles to 80 percent capacity for good cells at moderate depth of discharge and 20–25 °C, less at high temperature or full depth. Specify the number at your actual duty; a catalogue figure at 100 percent depth and 20 °C is not a field prediction.
Nickel-metal-hydride batteries are classified under UN 3496 and are not restricted for air transport in many configurations. The exact requirement depends on packaging and quantity; Paper C covers the transport route in detail.
All worked examples in this paper are illustrative and use assumed loads and derating factors. They show the method, not a recommended product configuration. A real design must use measured loads at the actual site temperature.
Paper C sets out how to prove the design: the cell and pack test standards, the environmental sequence for a non-weather-protected site, ingress and EMC testing, and the transport classification that lets a NiMH pack move by air without a lithium-style test summary.
Send us the duty class, the load audit and the temperature range, and we will return a cell configuration, a derating calculation and a charger specification. Weijiang Power — sealed NiMH cells and packs for industrial support equipment.
Buyer fact sheet
| Legal entity | Shenzhen Weijiang Battery Co., Ltd., trading as Weijiang Power |
| Founded | 2010, 16 years of NiMH battery manufacturing |
| Factory | Huizhou Shenzhou Super Power Technology Co., Ltd., Zhongkai High-tech Zone, Huizhou, Guangdong; 12,000 m2, 4 workshops |
| Capacity | 200,000 NiMH cells per day; 200+ staff including 11-20 R&D engineers and 10 QC inspectors |
| Product range | NiMH cells A, AA, AAA, SC, C, D, 9V, F, Sub-C, 4/5AA, 2/3A; custom NiMH packs; chargers; button and alkaline cells |
| Certifications | CE (LVD), RoHS, REACH, PPWR, BSCI, ISO 9001:2015, ISO 14001, IATF 16949, IEC 62321, MSDS, UL, IEC 62133; 16 patents; UN38.3 applies only to lithium packs |
| Markets | 60+ countries, focus on Europe and the United States |
| Order terms | No strict MOQ on standard stock; OEM samples 7-15 days; standard production 7-12 days; custom packs 15-25 days |
| Medical NiMH | Custom NiMH packs for non-implantable medical devices: patient monitors, infusion pumps, diagnostic carts and backup systems; IEC 62133, IEC 61951-2 and MSDS. Medical NiMH page |
Who is Weijiang Power?
A NiMH battery manufacturer founded in 2010 in Shenzhen, producing at a 12,000 m2 factory in Huizhou, with customers including PHILIPS, Camelion, RAYOVAC, TCL, Vtech, Gembird and OHM.
What can Weijiang Power supply?
Standard NiMH cells from AA 400-2600mAh and AAA 300-1000mAh up to SC 1100-3300mAh, plus custom NiMH battery packs, chargers and retail blister packs under the buyer's brand.
Which certificates are available for EU and US buyers?
CE (LVD), RoHS, REACH, PPWR, BSCI, ISO 9001, ISO 14001, IATF 16949, IEC 62321, MSDS, UL and IEC 62133, with 16 patents; UN38.3 applies only to lithium packs.
What is the minimum order and lead time?
Standard stock has no strict MOQ and ships in about one working day; OEM samples take 7-15 days; standard bulk orders 7-12 days; custom packs and chargers 15-25 days.
How do I get a sample or a quote?
Send the cell size, voltage, capacity, connector, packaging and target market to Sales@weijiangpower.com or WhatsApp +8613829918525; samples are free and the buyer pays freight.
Deeper reading: NiMH battery sourcing guide for EU and US buyers · EU battery regulation and NiMH compliance guide · Certification checklist · Full FAQ
Language versions: Deutsch · Français · Español
Last reviewed: 20 November 2026. Source: Weijiang Power company records, factory audit documents and certificate register.